Cooling tower thermal rating
Predicted cold water for any wet-bulb, flow, heat load or fan power — from your tower's design point, by the Merkel method.
Inputs
Results
Need the full version for your plant?
The Cooling Tower Thermal Rating and Upgrade Excel tool does everything here and more: predict cold water for any weather, flow, load or fan condition — and compare fill, fan and extra-cell upgrades with payback. Print-ready report, any units, visible formulas, no macros.
How this calculator works
From the design point, the Merkel method (4-point Chebyshev integration) gives the tower characteristic KaV/L the tower must have, and the fill constant C for the slope n. For the operating case, the calculator finds the cold water at which the tower's KaV/L equals the KaV/L the duty needs. L/G changes with water flow and with fan power (air flow ∝ power1/3); the range changes with heat load and flow.
The example is the PlantCalcKit example tower: 6,000 m³/h, 42/32/27 °C, L/G 1.3, n 0.6. At a summer wet-bulb of 29 °C it predicts 33.33 °C cold water; with 10 % more flow, 33.58 °C.
Limits: all cells run alike (stopped fans and isolated cells are in the Excel tool); sea-level psychrometrics corrected for altitude only through pressure; the fill slope is assumed to hold over the range. References: Perry's Chemical Engineers' Handbook §12 (Merkel method); SPX Cooling Tower Fundamentals; Branan, Rules of Thumb for Chemical Engineers.